Product data sheet
Characteristics
RXM4AB1MD
Miniature Plug-in relay - Zelio RXM 4 C/O 220
V DC 6 A
Main
Range of product
Zelio Relay
Miniature
Series name
Product or component
type
Plug-in relay
Device short name
RXM
Contacts type and com-
position
4 C/O
Control circuit voltage
220 V DC
[Ithe] conventional en-
closed thermal current
6 A at -40...55 °C
Status LED
Without
Control type
Lockable test button
20 %
Utilisation coefficient
Complementary
Shape of pin
Flat
[Ui] rated insulation voltage
300 V conforming to UL
300 V conforming to CSA
250 V conforming to IEC
[Uimp] rated impulse withstand voltage
Contacts material
2.5 kV for 1.2/50 µs
AgNi
[Ie] rated operational current
8 A at 30 V DC conforming to UL
6 A at 277 V AC conforming to UL
6 A at 250 V AC (NO) conforming to IEC
6 A at 28 V DC (NO) conforming to IEC
3 A at 250 V AC (NC) conforming to IEC
3 A at 28 V DC (NC) conforming to IEC
Maximum switching voltage
Resistive rated load
250 V conforming to IEC
6 A at 28 V DC
6 A at 250 V AC
Maximum switching capacity
Minimum switching capacity
Operating rate
1500 VA/168 W
170 mW at 10 mA, 17 V
<= 18000 cycles/hour no-load
<= 1200 cycles/hour under load
Mechanical durability
Electrical durability
10000000 cycles
100000 cycles for resistive load
Average coil consumption in W
Drop-out voltage threshold
Operate time
0.9 W
>= 0.1 Uc
20 ms
Release time
20 ms
Average coil resistance
Rated operational voltage limits
Protection category
Operating position
48400 Ohm at 20 °C +/- 10 %
176...242 V DC
RT I
Any position
Product weight
0.037 kg
May 27, 2015
1