General Purpose Relays
SCHRACK
Power PCB Relay RX2 (Continued)
Coil versions, AC-coil 50Hz
Coil
Rated
Operate
voltage
50 Hz
VAC
Release
voltage
50 Hz
VAC
Coil
Rated coil
power
50 Hz
VA
code
voltage
resistance
VAC
24
115
230
Ohm
524
615
730
18.0
86.3
3.6
350+10%
8100+15%
32500+15%
0.76
17.3
34.5
0.76
0.74
172.5
All figures are given for coil without preenergization, at ambient temperature +23°C
Insulation
Dielectric strength coil-contact circuit
open contact circuit
4000 Vrms
1000 Vrms
2500 Vrms
W 8 / 8 mm
W 3 / 4 mm
W IIIa
adjacent contact circuits
Clearance / creepage coil-contact circuit
adjacent contact circuits
Material group of insulation parts
Tracking index of relay base
Insulation to IEC 60664-1
Type of insulation coil-contact circuit
open contact circuit
PTI 250 V
reinforced
functional
basic
PCB layout / terminal assignment
Bottom view on solder pins
adjacent contact circuits
Rated insulation voltage
250 V
Pollution degree
3
2
Rated voltage system
240 V
400 V
Overvoltage category
III
Other data
RoHS - Directive 2002/95/EC
Flammability class according to UL94
Ambient temperature range
Operate- / release time DC coil
Bounce time DC coil, NO / NC contact
Vibration resistance (function) NO / NC contact
Shock resistance (destruction)
Category of protection
compliant as per product date code 0413
V-0 1)
-40...+70°C
typ 7 / 2 ms
typ 1 / 3 ms
20 / 4 g, 10 ... 150 Hz
100 g
S0418-CA
*) With the recommended PCB hole sizes a grid
pattern from 2.5 mm to 2.54 mm can be used.
RTII - flux proof
pcb or on socket
pcb
Mounting standard version (white cover)
transparent version
Mounting distance
2,5 mm 2)
2 CO contacts
Resistance to soldering heat flux-proof version
Relay weight
270°C / 10 s
14 g
500 pcs
Packaging unit
1) Version with transparent cover: V-2
2) Version with transparent cover: 5 mm
S0163-BJ
Accessories
For standard version (white cover), details see
accessories RT
Dimensions
S0272-BA
2
Datasheet
Rev. GG1
Dimensions are in mm unless
Product specification
processing information
‘Schrack’ section.
Issued 2007/07
otherwise specified and are
shown for reference purposes
only.
according to IEC 61810-1.
Product data, technical para-
meters, test conditions and
only to be used together
www.tycoelectronics.com
www.schrackrelays.com
with the 'Definitions' at
schrackrelays.com in the
Specifications subject to
change.