General Information
The following information must be strictly adhered to in order to guarantee the terminal block electrical, mechanical and environmental performance.
Protection
Rail
IP 20
NEMA 1
DIN3-TH35
Wire stripping length
10.5 mm
0.413 in
Screw clamp
Screw rail contact
(Maximum value)
Flat screwdriver
Operating tool
Torque
4 mm
0.157 in
0.85 Nm
0.15 Nm
7.52 lb.in
1.33 lb.in
0.15 Nm
1.33 lb.in
Mechanical endurance
of disconnect system
Material Specifications
Insulating material
IRC
Polyamide
600 V
Flammability
UL94 V0
NF F 16 101 I2F2
Needle flame test IEC 60695-11-5 Compliant
Connecting capacity per clamp
1 Rigid conductor
1 Flexible conductor without ferrule
1 Flexible conductor with ferrule
0.2-6 mm²
0.22-6 mm²
0.22-4 mm²
24-10 AWG
24-10 AWG
24-10 AWG
Ferrule maximum outer diameter
5.5 mm 0.216 in
Multi Connecting capacity per clamp
2 Rigid conductors
2 Flexible conductors without ferrule
2 Flexible conductors with twin ferrule
Don't mix solid and flexible conductors in the same clamp
Don't mix solid or flexible conductors of different sizes in the same clamp
The "Connecting capacity with ferrule " data is guaranteed with ABB crimping tool PS-3
Cross section
Rated cross section
6 mm²
6 mm²
10 AWG
10 AWG
Maximum Cross section
Manufacturer data
Manufacturer data
Gauge
A4-B3 / 3 mm / 0.118 in / IEC 60947-7-1
Electrical characteristics
Current
Rated current
IEC 60947-7-1
UL 1059
Field and factory wiring Cat.2
Factory wiring Cat.1
UL 1059
CSA-C-22.2 n° 158
Rated short-time withstand current 1 s (Icw)
720 A
Short-time withstand current
0.5 s
5 s
Manufacturer data
Manufacturer data
Manufacturer data
Manufacturer data
Manufacturer data
CSA-C-22.2 n° 158
Manufacturer data
Manufacturer data 720 A
10 s
30 s
1 mn
Rated short circuit withstand
Max. current (45° temperature increase) / Max. cross section (mm²)
Maximum short circuit current (1s)
6 mm²
2